Terminal Blocks

UL 1059 vs IEC 60947-7-1 for Terminal Blocks

Tags:

UL 1059 and IEC 60947-7-1 both address terminal blocks, but an approval under one system does not automatically establish an equivalent rating under the other. The practical task is to select the correct certified product, then apply the voltage, current, conductor and installation conditions shown in its certification record and datasheet.

Quick Comparison

Parameter IEC 60947-7-1 UL 1059
Region International (Europe, Asia) North America (US, Canada)
Rated voltage (typical) Up to 1000V 300V or 600V
Current rating basis Declared rating supported by the applicable test program Certified rating for specified conductor and use conditions
Wire size mm² AWG
Torque test Per manufacturer spec UL-specified torque values
Short-circuit test SCCR tested (1.5–10 kA) SCCR tested
Loaded-pole / grouping effect Use manufacturer application data and test conditions Use certified rating and manufacturer application data; no universal conversion factor
Creepage/Clearance IEC 60664-1 UL 840
Flammability Material and product requirements depend on construction and application Material and product requirements depend on construction and certification
Marking / documentation Ratings and connection data are supplied as required Ratings and conditions are shown on the product, packaging, datasheet or certification record as applicable

1. Why Two Standards Matter

If equipment is evaluated for both international and North American markets, the terminal block must be acceptable under the equipment’s certification path in each market. A component certificate is not a blanket approval for every installation; the end-product evaluator also checks the component’s ratings and conditions of acceptability.

Dual-Certified Terminals

Many terminal blocks are offered with both IEC and UL ratings. A dual-approved terminal may show values such as:

  • IEC rating: 16A / 500V / 2.5mm²
  • UL rating: 15A / 300V / 14 AWG

The lower printed value is not automatically the only design limit: each market uses its own rating and installation conditions. A global design can use a common conservative limit, or maintain market-specific ratings when the product documentation and certification support them.


2. Current Rating Differences

Cross-Section IEC Rating (typical) UL Rating (typical) Difference
1.5mm² (16 AWG) 16A 10–12A UL 20–25% lower
2.5mm² (14 AWG) 24A 15–20A UL 17–40% lower
4mm² (12 AWG) 32A 20–25A UL 22–38% lower
6mm² (10 AWG) 41A 30A UL 27% lower
10mm² (8 AWG) 57A 40–50A UL 12–30% lower

These examples illustrate why ratings should not be converted by percentage. Differences can arise from conductor designation, test setup, temperature limits, spacing, product category and the exact certification program. Use the values assigned to the selected part number.


3. Loaded Positions and Derating

Long terminal strips and multi-position PCB connectors can retain more heat than a single loaded pole. The appropriate reduction depends on the certification conditions and the manufacturer’s derating data. Do not apply a universal “UL 80% rule” to every terminal block; an 80% factor may be used in some engineering practices or curve construction, but it does not replace the part-specific record.

Design Impact

Circuit IEC-Labeled Design Example UL-Labeled Design Example
Required current 20A 20A
Published part rating 24A under stated IEC conditions 15A under stated UL conditions
Action Verify loaded-pole and ambient derating Select a higher-rated certified part or reduce circuit current

The limiting approval may require a larger terminal, larger conductor or lower circuit current. Confirm the result against the exact certification and end-product standard.


4. Creepage and Clearance

Standard Reference Design Approach
IEC 60947-7-1 IEC 60664-1 principles as applicable Determine from working voltage, overvoltage category, pollution degree, material group and field conditions
UL 1059 UL spacing and construction requirements as applicable Use the certified voltage rating, product group and installation conditions

Creepage and clearance are affected by more than nominal voltage. Pollution degree, impulse withstand, insulation material, coating, field-wiring category and end-product requirements all matter. Pitch alone cannot establish a voltage rating.


5. Global-Market Selection Checklist

  1. Identify the end-product standard and destination markets.
  2. Confirm the exact terminal part number appears in the relevant certification record.
  3. Compare rated voltage, current, conductor range, conductor type, strip length and torque.
  4. Check whether accessories, jumpers and PE terminals are covered by the same system approval.
  5. Apply ambient and loaded-position derating from the manufacturer.
  6. Verify creepage, clearance, insulation coordination and enclosure conditions in the end product.
  7. Keep the certification record, datasheet revision and installation instruction in the technical file.

Common Questions

Does CE marking mean a terminal block is UL Listed?

No. CE marking and UL certification serve different regulatory and conformity-assessment purposes. Verify the North American certification mark and record for the exact part.

Is an IEC current rating valid in a UL panel?

Use the current rating and conditions recognized for the UL application. The IEC value may remain useful for another market, but it does not replace the North American certified rating.

Can one global part number have two ratings?

Yes. A dual-approved terminal may carry different IEC and UL ratings. Document both and use the applicable value for each market—or use one conservative common design limit when appropriate.


6. Documents to Confirm Before Purchase

Requirement Evidence to Obtain
UL application Certification record for the exact part number, including ratings and conditions of acceptability
IEC application Applicable certificate/test documentation, datasheet and declaration supplied for the exact series
Canadian market Relevant Canadian certification record where required
CE-marked end product Supplier documentation needed for the equipment manufacturer’s conformity assessment
RoHS / REACH Current material declarations tied to the purchased part number

Request Certification Documents

GSConn can provide available UL file references, IEC documentation, ratings and installation conditions for the selected series. Confirm the exact part number and document revision before releasing a global-market design.